2 Zone Control Panel - RE – 101 Not Expandable

Add to Basket Big View View Catlog
Features:
Fully Confirms IS 2189
Modular Construction.
Battery Backup With Built-in Charging.
Error Free Fire / Fault Status in Unambiguous Colored LED indication.
Relay Output For Actuators.
Output For Remote Repeater Panel
Lamp Test Facility
Compatible to all Types of Conventional Detectors.
Twin RED LED indicator for fire.
24 V DC output for External notification devices (Sounder , Bell , etc)
Cross Zoning Facility
Indent to release LED Indication
Bypass Facility With LED Indication
Instant Release Push Button
Gas Released LED Indication
Output To Actuate Solenoid Valve
 
Specification :
No. of Zones : 20 Zones
Primary Power : 230 V AC, 50 Hz
Standby Power : 24 V DC Maintenance Free Rechargeable Battery (24V , 3 AH Battery)
Zone Input : 2 Wire loop with 4K7 End On Line Resistors (EOL)
Standard  Indications : System On /AC On /Battery On
Operating Voltage : 24V DC
Normal Loop Voltage : 20.4v DC
Operating Current : 30mA plus 4.2mA per Zone
Open Threshold Current : 4.2 mA
Short Circuit Threshold Current : 40 mA
Standby Threshold Current : 8.2 mA (EOL Current + Detector’s Current)
Alarm Output : Common Output (Non Supervised) :1A (Max)
Alarm Current : 20 - 35mA
Operating Conditions : -10° to 45°C, 30 – 90 % RH
Dimension : 350 (L) × 250 (H) × 100 (D) mm