| Features: |
 |
Fully Confirms IS 2189 |
 |
Modular Construction. |
 |
Battery Backup With Built-in
Charging. |
 |
Error Free Fire / Fault
Status in Unambiguous Colored LED indication. |
 |
20×4 LCD Dot Matrix
Display. |
 |
Lox Battery / Battery Fail
Warning Audio / Visual Display. |
 |
Charger ON indication. |
 |
A.C Fail Audio / Visual
Warning. |
 |
Relay Output For Actuators. |
 |
Output For Remote Repeater
Panel. |
 |
Lamp Test Facility. |
 |
One Man Walk Test Facility |
 |
Compatible to all Types
of Conventional Detectors. |
 |
Separate Twin LED Indication
For Fire. |
 |
Zone Isolation Facility
With Loop Voltage Cut off. |
 |
On Site Location Programming
Facility. |
 |
User, Installer & Maintenance
Friendly. |
 |
Password Protection. |
 |
24v DC Output For External
Notification Devices.[Sounders, Bell etc.,] |
 |
Optional Loop Sounder. |
 |
Optional Twin LED for MCP
Activation. |
 |
Optional RS 232 Communication
Facility. |
 |
Optional RS 485 Communication
Facility For Remote Annunciation Panel. |
| |
| Specification: |
 |
No. of Zones : 16 Zones |
 |
Primary Power : 230v AC,
50 Hz |
 |
Standby Power : 24v DC (2nos.
of 12v, 7Ah S.M.F. Battery) |
 |
Zone Input : 2 Wire loop
With 4K7 End Of Line Resistors[EOL] |
 |
Standard Indications
: System On /AC On /Battery On / Low Battery/Charger
On /Walk Test / Auxiliary Trip |
 |
Operating Voltage : 24v
DC |
 |
Normal Loop Voltage : 20.4v
DC |
 |
Operating Current : 80mA
plus 4.2mA per zone |
 |
Open Threshold Current :
4.2 mA |
 |
Short Circuit Threshold
Current : 40 mA |
 |
Standby Threshold Current
: 8.2 mA (EOL Current + Detector’s
Current) |
 |
Alarm Current : 20-35 mA |
 |
Operating Conditions : -10° to
45°C, 30 - 95 % RH |
 |
Dimension : 350 × 300 × 100
(all are in mm)s |